Dear Campbell Develop Engineer,
We want to upgrade our system,because our datalogger has broken, we used two AM416 to read 68 vibratingwire sensors, AM416 connected to CR10x through AVW4.[CR10X ->AVW4 ->two AM416 ->68 sensors
]
I want to change CR10X with CR1000, it's possible to do that? because i have tried to make a program using ShortCut, and there's not provide AVW4 to connect with two AM416. It's only provide AVW200 connnect to two AM16/32B. I only want to change datalogger, If it is possible to do that, how to input Zero reading / gauge factor in every single sensor? Any ideas?
Thanks before
LoggerNet software includes a program called Transformer, which will generate a CR1000 program from a CR10X program. You will need to check the program carefully to make sure everything runs correctly, but it does give you a good start on the new program.
Regards,
Dana W.