no voltage at the dataloger CR1OOO_Campbellsci论坛问答

HELLO...I Have the et107 weather station...the problem is that....the red led is glowing but no voltage at the dataloger...the batery is 13.7 v

no voltage at the dataloger CR1OOO_Campbellsci论坛问答

新对话如下:

Hi Lara,

Assuming the station has a PS100, the red light indicates a battery charging voltage is present, but not necessarily that the power supply is turned on. Double-check the toggle switch to make sure it is in the On position.

Also check the wiring between the PS100 and the battery terminals on the enclosure -- the leads should be secured in the 12 V terminal that is on the upper right of the enclosure wiring panel (assuming you are reading the text right side up).

You may want to take a look at the manual for reference:

http://www.campbellsci.com/documents/manuals/et107.pdf

Please note that Campbell Scientific is closed December 24 & 25 (and it's pretty quiet around here right now). We will be back in the office on Monday, the 28th.

Regards,

Dana W.